Protectofier 6642 - Combustion Safeguards
Operate with Flame Rod and/or P-C II Scanner

6642 Features
Modularized Multi-Burner Control
Time Proven Plug-in Solid State FLAME-PAK Amplifier
Plug-in, Interchangeable Relays
Plug-in Power Transformer
Flame Rod and/or Ultra-Violet Sensing. Independent or simultaneously using same FLAME-PAK Amplifier.
FORM 6642VA
Basic combustion safeguard model
FORM 6642VB
Breaker - lockout switch model
Required for automatic lighted installations. System "latches out" after failure to light within ignition trial time and cannot attempt restart until switch is manually reset.
Standard ignition trial time is 15 seconds. Also available in 10-second and 5-second trial time.
Form 6642VBNR - Automatic only and Non-relight.
FORM 6642VL
Load relay - included for all multi-burner models
FORM 6642VT
Timofier model plugin, fixed time assembly.
The timofier provides purge time and ignition trial time. The ignition trial time is deducted from the motor time cycle (1/2, 1, 1-1/4, 2, 3, 4, and 6 minutes available for manual and automatic models; 10 minutes for manual model only) to purge the time.
Standard ignition trial time is 15 seconds. Also available in 10-second and 5-second trial time.
Specify both purge and ignition times.
Purge time shall allow system to have a minimum of four fresh air changes.
FORM 6642VBL
Combines features of Breaker and Load relay models described above.
Form 6642VBLNR - Automatic only and Non-relight.
FORM 6642VBT
Combines features of Breaker and Timofier models described above.
Form 6642VBTNR - Automatic only and Non-relight.
FORM 6642VLT
Combines features of Load relay and Timofier models described above.
FORM 6642VBLT
Combines features of Breaker, Load relay, and Timofier models described above.
Form 6642VBLTNR - Automatic only and Non-relight.
FORM 6642FF
Full Feature Combustion Safeguard including:
Proof of Closure
Proof of High Fire Purge
Purge Timing (In 15 sec. increments, 7 min. 45 sec. max)
Proof of Low Fire Start
Ignition Trial Timing (Pilot) 10 sec.
Pilot Interrupt Timing (Main burner ignition trial) 10 or 15 sec.
Alarm output if the safety interlocks (limit switches) or flame failure causes shutdown.
Relay contacts available to drive actuator to high fire for purge, low fire for ignition trial, and control when main burner is proven.
Eight status lights