Protectofier 6642 -
Combustion Safeguards
Operate with Flame Rod and/or P-C II Scanner
-
6642 Features
- Modularized Multi-Burner Control
- Time Proven Plug-in Solid State FLAME-PAK
Amplifier
- Plug-in, Interchangeable Relays
- Plug-in Power Transformer
- Flame Rod and/or Ultra-Violet Sensing. Independent or
simultaneously using same FLAME-PAK Amplifier.
- FORM 6642VA
- Basic combustion safeguard model
- FORM 6642VB
- Breaker - lockout switch model
- Required for automatic lighted installations.
System "latches out" after failure to light within ignition trial time
and cannot attempt restart until switch is manually reset.
- Standard ignition trial time is 15 seconds.
Also available in 10-second and 5-second trial time.
- Form 6642VBNR - Automatic only and Non-relight.
- FORM 6642VL
- Load relay - included for all multi-burner models
- FORM 6642VT
- Timofier model plugin, fixed time assembly.
- The timofier provides purge time and ignition trial time.
The ignition trial time is deducted from the motor time cycle
(1/2, 1, 1-1/4, 2, 3, 4, and 6 minutes available for manual and automatic
models; 10 minutes for manual model only) to purge the time.
- Standard ignition trial time is 15 seconds.
Also available in 10-second and 5-second trial time.
- Specify both purge and ignition times.
- Purge time shall allow system to have a minimum of four
fresh air changes.
- FORM 6642VBL
- Combines features of Breaker and Load relay models described above.
- Form 6642VBLNR - Automatic only and Non-relight.
- FORM 6642VBT
- Combines features of Breaker and Timofier models described above.
- Form 6642VBTNR - Automatic only and Non-relight.
- FORM 6642VLT
- Combines features of Load relay and Timofier models described above.
- FORM 6642VBLT
- Combines features of Breaker, Load relay, and Timofier models described above.
- Form 6642VBLTNR - Automatic only and Non-relight.
- FORM 6642FF
- Full Feature Combustion Safeguard including:
- Proof of Closure
- Proof
of High Fire Purge
- Purge Timing (In 15 sec. increments, 7 min. 45 sec. max)
- Proof of Low Fire Start
- Ignition Trial Timing (Pilot) 10 sec.
- Pilot Interrupt Timing (Main burner ignition trial) 10 or 15 sec.
- Alarm output if the safety interlocks (limit switches) or flame failure causes shutdown.
- Relay contacts available to drive actuator to high fire for purge, low fire for ignition trial, and control when main burner is proven.
- Eight status lights
-
|
|